BD Module:LX3V-2ADI2DAI-BD/LX3V-2ADV2DAV-BD

2 * Analog Input/ Analog Output (4~20mA)

2 * Analog Input/ Output (-10V~10V)


Software&manual Inquiry sales@we-con.com.cn
Specification


ItemLX3V-2ADI2DAI-BDLX3V-2ADV2DAV-BD
Power supply24VDC±10%, 50mA; 5VDC±10%, 70mA (Powered by PLC host)
Analog input (ADI)Analog input (ADV)
Analog input rangeDC 4~20mA (input resistance 250KΩ). Absolute maximum input: -2mA, +30mADC-10V~10V (input resistance 160KΩ). Note: If the input voltage exceeds ±15V, the unit will be damaged.
Rated  range4~20mA: 0~2000-10V~10V: -2000~2000
The maximum display range-500~2048-2048~2048
Resolution8uA[4mA ~20mA / 2000 ]5mV[10V default scope 1/2000]
Precision±0.5% of full scale (4~20mA:±0.08mA)±0.5% of full scale
AD conversion timeOne PLC scanning cycle
Input characteristicsimage.pngimage.png
InsulationNo insulation in each PLC channel
Occupied pointsNone
Analog output (DAI)Analog output (DAV)
Rated range4~20mA: 0~2000-10V~10V: -2000~2000
Analog outputDC 4~20mA (the external load resistance is no less than 500Ω)DC-10V~10V (the external load resistance is no less than 2KΩ)
Digital output12 bit binary
Resolution8uA[4~20mA / 2000]5mV[10V default scope 1/2000]
Precision±0.5% of full scale
AD conversion timeOne PLC scanning cycle
Input characteristics

The external load is 250Ω and 0-2000 is converted to 4-20mA



image.png

image.png
InsulationNo insulation in each PLC channel
Occupied pointsNone